Surface Water Drainage
Installation design – radii, crossings, junctions and
bends
Radii
Highway/Mini Highway:
- To form external radii of 25 metres or less (minimum 6 m),
special radius units should be used (see table below). As these do
not cover all individual radius dimensions, some slight gaps are
required between units as indicated in Highway radii gap widths
table.
- For external radii greater than 25 metres, lay straight units
with open joints.
- To form internal radii (minimum 6 metres), use 7/6 internal
radius units.
Clearway/Safeticurb:
- Where necessary, standard (straight) units may be laid to form
radii or bends.
- Safeticurb units: alignment ring within bore acts as a former
for infill mortars to seal joint.
Crossings
Highway/Mini Highway:
- Use crossing base units to carry drainage runs under side roads
/ vehicular crossing points Grid units available.
- Safeticurb (DBK unit only):
- To continue linear drainage at road junctions, kerb crossing
points (pedestrian/vehicular), use transition units to reduce kerb
height to road level. These connect with standard grid or slot
units as necessary.
Junctions/sharp bends
Clearway/Safeticurb:
- Use silt box top at outlets or with suitable uPVC pipe fittings
(cut to fit) to form junctions or sharp bends.
Highway radii gap widths
| Radius (m) |
Radius unit reference |
Top and base gap |
| 6 |
7/6 |
2 |
| 7.5 |
10/8 |
3 |
| 9 |
10.8 |
2 |
| 10.5 |
25/11 |
4 |
| 12 |
25/11 |
1 |
| 15 |
25/11 |
2 |
| 20 |
25/11 |
5 |
| 25 |
25/11 |
7 |
| 26 |
Straight |
7 |
Installation design – units
General principles
All units are unreinforced: protect from stresses caused by
thermal expansion of cementitious paving materials. Leave 1mm gap
between each unit to prevent damage from thermal expansion of the
units themselves.
Expansion joints MUST be installed on each side of drainage runs
in concrete pavements or those incorporating a cement bound/lean
mix concrete roadbase.
DO NOT place these joints directly adjacent to any trafficked
unit as this would allow units to rock under trafficking and may
allow water ingress into the base or sub-grade.
Recommended position of joints (minimum distances):
- 600 mm from Clearway/Safeticurb units.
- 125 mm from Highway units.
Note: As Highway units are not regularly
trafficked, expansion joints could be placed directly against them.
However, 125 mm distance is recommended to avoid ingress of water
between the unit and carriageway construction.